An important addition to the THERMOFLEX® line of heat detectors is the Multiple Circuit unit. Two separate sets of contacts are available in the following configurations: two Normally Open (N/O) contacts, two Normally Closed (N/C) contacts, or one N/O and one N/C. Any THERMOFLEX® detector can be ordered in the Multiple Circuit configuration, regardless of its operation as a rate-of-rise / fixed temperature, or fixed temperature only, with any one of the four fixed temperature ratings (135º, 165º, 200º and 285º F.) Multiple Circuit detectors are also available as Moisture Proof (see Spec. Sheet #2) and Explosion Proof (see Spec. Sheet #4). The Multiple Circuit detector has a suffix that describes it contact configuration:
Multiple Circuit Detector, rear view, indicating one N/O contact and one N/C Contact. "N/C" is referred to in French as "N/F".
The Model CR 135-2 is a combination Rate-of-Rise
and Fixed Temperature detector. Two sets of normally open contacts will
close when the ceiling temperature increases at a (minimum) rate of 8.4
Celsius degrees (15 F. Degrees) per minute. Closing one contact initiates
the fire alarm sequence while closing the other contact could sound a
local audible or activate a local annunciation device. Independent of the
rate-of-rise operation, the fixed temperature portion consists of a
spring-loaded plunger retained by a fusible alloy that releases when the
ceiling temperature reaches 57 degrees Celsius, (135º F). When
released, the plunger strikes both sets of contacts and holds them closed.
The Model CR 135-2C contains two Normally Closed (N/C) sets of contacts, which both open when the rate-of-rise or fixed temperature portion of the detector operates. Multiple units are wired in series, and may be supervised by resistor depending on the type of Control Panel that is used. Closed Circuit is characteristic of Intrusion Alarm systems. The Model CR 135-2CO contains one Normally Closed (N/C) contact and one Normally Open (N/O) contact. Usually the N/O contact is used to initiate the Fire Alarm, and the N/C contact is used as a releasing device for a local door or for shutting down specific machinery or equipment. Note 1 : The designation "CF" in the model number denotes "Fixed Temperature Only" operation. The three-digit number following denotes the temperature at which the plunger is released ( 135º, 165º, 200º or 285º F.), permanently operating the contacts. For Example: CF 200-2CO describes a detector that is Fixed Temperature Only, fusing at 200º F., containing one N/C contact and one N/O contact. Note 2: All Multiple Circuit detectors are available as Moisture Proof or Explosion Proof. Specify with suffixes "MP" or "EWT" respectively. For example: CR 135-2 MP describes a detector that is a combination rate-of-rise and fixed temperature unit, fusing at 135º F., containing two N/O contacts, assembled with a Moisture Proof seal plate, and has four sets of pig-tail leads (2 per each set of contacts). Contact Rating: 3A @ 125 VAC * 1A @ 28 VDC * 0.3A @ 125 VDC 0.1A @ 250 VDC Dimensions: Diameter: 5.25" (13.4 cm) Height: 2.0" (4.85 cm) Weight: 0.34 lb. (156 gm)
|
|
|
|
|
|
|